Heat Output

Consider the heat dissipation ratings of equipment to determine cooling requirements. Additional cooling equipment may be required. The following table shows the heat output of the InfraStruXure PDU and the Symmetra PX UPS.

InfraStruXure PDU

208V

6,165BTU/hr. (1.81kW)

480V

5,079BTU/hr. (1.49kW)

600V

5,527BTU/hr. (1.62kW)

 

 

Symmetra PX UPS

23,757BTU/hr. (6.96kW)

 

 

The heat output is higher while batteries are charging. Under normal operating conditions, battery recharging periods are infrequent.

Note