Top-Level Menu
Control Logging
Status Display
Setup Diags
Accessories Help
Control Menu
UPS Into Bypass Do Self Test Simulate Power Fail Graceful Reboot
Graceful Turn Off
Start Runtime Cal Turn Load Off
Confirmation Screen
Confirm
Yes, UPS Load OFF No, Abort

Start-Up Procedure: InfraStruXure System

The UPS interface displays the following fault screen:

f. Press any key.

Bypass not available

Input Freq/Volt out of range

Press any key...

The UPS interface displays the following fault screen:

g. Press the ESC key.

End of Fault List Press Esc to exit or other keys to view list again

The LOAD ON LED illuminates and the interface displays the following screen:

UPS load is on

Press any key...

After you have verified that the UPS operates correctly in on-battery operation, shut-down the UPS:

3. Command the UPS to turn off power to the load: a. Press the ESC key at the top-level status

screen to open the top-level menu and have access to eight submenus.

b. Select Control, and press the ENTER key.

c. Select Turn Load Off from the Control menu, and press the ENTER key.

d. On the next screen: select Yes, UPS Load OFF, and press the ENTER key.

The LOAD ON LED turns off and the interface displays the following two screens:

UPS has been

commanded to turn load power off...

UPS load is off

Press any key...

InfraStruXure System—Installation and Start-Up

55