Start-Up Procedure: InfraStruXure System
The interface will display the following fault message: e. Select Start up on Batt, and press the
ENTER key.
Low/No AC input
Start up on Batt? Start Now
The interface will display the following screen:
UPS has been
commanded to turn load power on...
The UPS interface displays the following fault screen: f. Press any key.
Bypass not available
Input Freq/Volt out of range
Press any key...
The UPS interface displays the following fault screen: g. Press the ESC key.
End of Fault List Press Esc to exit or other keys to view list again
The LOAD ON LED illuminates and the interface displays the following screen:
UPS load is on
Press any key...
5. Close (turn ON) the Q2 circuit breaker on the PDU.
InfraStruXure | 59 |