Start-Up Procedure: InfraStruXure System

The interface will display the following fault message: e. Select Start up on Batt, and press the

ENTER key.

Low/No AC input

Start up on Batt? Start Now

The interface will display the following screen:

UPS has been

commanded to turn load power on...

The UPS interface displays the following fault screen: f. Press any key.

Bypass not available

Input Freq/Volt out of range

Press any key...

The UPS interface displays the following fault screen: g. Press the ESC key.

End of Fault List Press Esc to exit or other keys to view list again

The LOAD ON LED illuminates and the interface displays the following screen:

UPS load is on

Press any key...

5. Close (turn ON) the Q2 circuit breaker on the PDU.

InfraStruXure System—Installation and Start-Up

59

Page 69
Image 69
American Power Conversion InfraStruXureTM System manual Close turn on the Q2 circuit breaker on the PDU