4.Set the UPS System Enable switch to the ON position.
The UPS will show a Forced Bypass message on the display interface, and the Fault LED will be red.
5.Command the UPS to apply power to the load:
a.Press the ESC key at the
b.Select Control, and press the ENTER key.
c.Select Turn Load On from the Control menu, and press the ENTER key.
Appendix A : System Operation
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
d.On the next screen: select Yes, UPS Load ON, and press the ENTER key.
Confirmation Screen
Confirm
Yes, UPS Load ON
No, Abort
The LOAD ON LED illuminates and the interface displays the following two screens:
UPS has been
commanded to turn load power on...
UPS load is on
Press any key...
6. Command the UPS into static bypass operation through the UPS display interface:
a.Press the ESC key at the
b.Select Control on the
ENTER key.
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
InfraStruXure | 71 |