American Power Conversion InfraStruXureTM System manual Confirm Yes, UPS Load on No, Abort

Models: InfraStruXureTM System

1 100
Download 100 pages 51.56 Kb
Page 81
Image 81

4.Set the UPS System Enable switch to the ON position.

The UPS will show a Forced Bypass message on the display interface, and the Fault LED will be red.

5.Command the UPS to apply power to the load:

a.Press the ESC key at the top-level status screen to open the top-level menu and have access to eight submenus.

b.Select Control, and press the ENTER key.

c.Select Turn Load On from the Control menu, and press the ENTER key.

Appendix A : System Operation

Top-Level Menu

 

 

 

 

 

 

Control

Logging

 

 

Status

Display

 

 

Setup

Diags

 

 

Accessories

Help

 

 

 

 

Control Menu

UPS Into Bypass

Do Self Test

Simulate Power Fail

Graceful Reboot

Graceful Turn Off

Start Runtime Cal

Turn Load On

d.On the next screen: select Yes, UPS Load ON, and press the ENTER key.

Confirmation Screen

Confirm

Yes, UPS Load ON

No, Abort

The LOAD ON LED illuminates and the interface displays the following two screens:

UPS has been

commanded to turn load power on...

UPS load is on

Press any key...

6. Command the UPS into static bypass operation through the UPS display interface:

a.Press the ESC key at the top-level status screen to open the top-level menu.

b.Select Control on the top-level menu, and press the

ENTER key.

Top-Level Menu

 

 

 

 

 

 

Control

Logging

 

 

Status

Display

 

 

Setup

Diags

 

 

Accessories

Help

 

 

 

 

InfraStruXure System—Installation and Start-Up

71

Page 81
Image 81
American Power Conversion InfraStruXureTM System manual Confirm Yes, UPS Load on No, Abort