Start-Up Procedure: InfraStruXure System
62 InfraStruXure System—Installation and Start-Up
Return from maintenance bypass operation
2. Close (turn ON) the Q2 circuit breaker on the InfraStruXure PDU.
1. Command the UPS into static bypass operation through the UPS display interface:
a. Press the ESC key to open the top-level
menu.
Top- Lev el M enu
b. Select Control on the top-level menu, and
press the ENTER key.
c. Select UPS Into Bypass on the Control
menu, and press the ENTER key.
Control Menu
d. On the next screen: select Yes, UPS into
Bypass, and press the ENTER key.
Confirmation Screen
Note
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to
operate the Q2 circuit breaker.
Note
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe
to operate the Q3 circuit breaker
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort