Appendix A : System Operation

c.Select UPS Into Bypass on the Control menu, and press the ENTER key.

Control Menu

UPS Into Bypass

Do Self Test

Simulate Power Fail

Graceful Reboot

Graceful Turn Off

Start Runtime Cal

Turn Load On

d.Confirm the selection on the next screen: select Yes, UPS into Bypass, and press the ENTER key.

Confirmation Screen

Confirm

Yes, UPS into Bypass No, Abort

The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate the Q2 circuit breaker.

Note

7. Close (turn ON) the Q2 circuit breaker on the PDU.

The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to operate the Q3 circuit breaker

Note

8. Open (turn OFF) the Q3 circuit breaker on the PDU.

The UPS automatically comes out of Static Bypass operation.

72

InfraStruXure System—Installation and Start-Up