Mounting 110A- or 110P-type terminal blocks on the wall
Issue 3 January 2008 21
Mounting 110A- or 110P-type terminal blocks on the wall
The 110A-type terminal blocks can be stacked in almost any arrangement at any height or
location on the wall. Figure 5: 110A-type terminal blocks (300-pair) on page 22 shows one
arrangement. The distance between the mounting screw holes on the terminal blocks is 10.8
inches (27.4 centimeters). If a vertical patch cord trough is used, the distance between the
mounting screw holes is 5.31 inches (13.3 centimeters).
With 110P-type terminal blocks, the first block of the trunk/auxiliary field is aligned with the left
side of the media gateway. See Figure6: 110P-type terminal blocks (900-pair)on page 23.
This arrangement allows for growth on the right side of the MDF.
To mount 110A- or 110P-type terminal blocks:
1. Route the cables from the rear of the media gateway stack to the MDF via the Cable Slack
Manager. See Installing Cable Slack Managerson page 25.
2. If you are installing 300-pair terminal blocks, draw a level horizontal line on the wall 47.5
inches (1.2 meters) above the floor. See Figure5: 110A-type terminal blocks (300-pair)on
page 22.
If you are installing 900-pair terminal blocks, draw a level horizontal line on the wall 23
inches (58.4 cm) above the floor. See Figure6: 110P-type terminal blocks (900-pair)on
page 23.
3. To mount the first trunk/auxiliary field terminal block, partially install 2 3/4-inch, #12 wood
screws, 7-11/1- inch (19.5-centimeter) apart on the left side of the horizontal line on the wall.
4. Slide the bottom terminal block ft onto the mounting screws and mark the upper mounting
screw locations.
5. Remove the terminal block and partially install the upper mounting screws.
6. Place the terminal block on the mounting screws and tighten the screws.
7. If installing a vertical patch cord trough, partially install the first screw for the patch cord
trough, on the line, 7/8-inch (2.2-centimeter) to the right of the previous screw. Partially
install the second mounting screw 5.31 inch (13.5 centimeter) to the right of the screw just
installed. Repeat Steps 4, 5, and 6.
8. If another trunk/auxiliary field terminal block is to be installed, partially install the first screw
for the terminal block, on the line, 7/8-inch (2.2-centimeter) to the right of the previous
screw. Partially install the second mounting screw 7-11/1- inch (19.5-centimeter) to the right
of the screw just installed. Repeat Steps 4, 5, and 6.
9. If a horizontal patch cord trough is to be installed, install it, on the line, between the trunk/
auxiliary field and the distribution field.
10. To install the first distribution field terminal block, partially install 2 3/4-inch, #12 wood
screws, 7-11/16 inch (19.5 centimeter) apart on the line, to the right of the vertical patch
cord trough. Repeat Steps 4, 5, and 6.