Installing and administering the patch cord/jumper

Connecting expansion control carrier outputs cable (MCC1 Media Gateway only)

To connect the expansion control carrier outputs cable:

1.Plug the connector cable in the AUX connector on the rear of the expansion control carrier.

2.Route the connector cable through the cable slack manager to the assigned 110-type terminal block in the yellow field of the trunk/auxiliary field.

Connecting trunk pairs using concentrator cables

Figure 31: Connect trunk pairs using concentrator cables on page 66 shows trunk pairs connected to the media gateway with concentrator cables. To install the cables:

1.Connect B25A cables between the network interface and sneak fuse panels.

2.Connect A25D cables from the sneak fuse panels to the 110-type terminal block connectors in the green field.

3.Connect patch cords/jumper wires from the terminal block in the green field to the associated terminal block in the purple field.

4.Connect the single-fingered end of the concentrator cables to the 110-type terminal block connectors in the purple field in Step 3.

5.Connect the other end (2/3-fingered end) of the concentrator cables to the appropriate carrier slots. Equipped carrier slots are identified on the CSD. Mark the nomenclature strips above the carriers to identify the slots.

6.Label connectors on each end of the cables that connect to the media gateway.

7.Route the cables down the sides of the media gateway and store the excess cable slack in the cable slack manager as previously described.

Issue 3 January 2008 65

Page 65
Image 65
Avaya 03-300686 manual Connecting trunk pairs using concentrator cables