Avaya IP600 manual Distribution Unit, Cabinet Type Circuit Breaker Size

Models: IP600

1 150
Download 150 pages 28.48 Kb
Page 19
Image 19

Hardware

1

The Avaya IP600 should be installed in a well-ventilated area. Maximum equipment performance is achieved at an ambient temperature between 40 and 120 °F (4 and

49 °C) for a short-term operation (not more than 72 consecutive hours or 15 days in a year) and up to 110 °F (43 °C) for a continuous operation.

The relative humidity range is 10% to 95% at up to 84 °F (29 °C). Above this, maximum relative humidity decreases from 95% down to 32% at 120 °F (49 °C). Installations outside these limits may reduce system life or affect operation. The recommended temperature and humidity range is 65 to 85 °F (18 to 29 °C) at 20% to 60% relative humidity.

The other Environmental Considerations and System Protection requirements described in the DEFINITY ECS Systems Description under “Site Requirements” apply to the Avaya IP600 as well.

Table 1. Cabinet Power Source Information

Cabinet Style and Power1

Power Sources

Power Input Receptacles

Distribution Unit

 

 

 

 

 

 

 

Rack Mount Cabinet. AC power

Single phase 120 VAC with neutral

120 VAC, 60

Hz NEMA 5-15R

supply (650A integrated power

Single phase 240 VAC with neutral

240 VAC, 50

Hz IEC 320

supply)

 

 

 

 

 

Japan installations use country

 

 

specific receptacles for 100 and

 

 

200 VAC, 50/60 Hz

 

 

 

 

1There is no integrated DC power supply. DC rectifiers can be used if desired; follow manufacturer’s instructions.

Table 2. Circuit Breakers for AC-Powered Cabinets

Cabinet Type

Circuit Breaker Size

 

 

Rack Mount Cabinet (120 VAC) 60 Hz

15 A

 

 

Rack Mount Cabinet (240 VAC) 50 Hz

10 A

 

 

Overview for Avaya IP600 Internet Protocol Communications Server

 

555-233-001 — Issue 5 — November 2000

7