The Avaya IP600 should be installed in a
49 °C) for a
The relative humidity range is 10% to 95% at up to 84 °F (29 °C). Above this, maximum relative humidity decreases from 95% down to 32% at 120 °F (49 °C). Installations outside these limits may reduce system life or affect operation. The recommended temperature and humidity range is 65 to 85 °F (18 to 29 °C) at 20% to 60% relative humidity.
The other Environmental Considerations and System Protection requirements described in the DEFINITY ECS Systems Description under “Site Requirements” apply to the Avaya IP600 as well.
Table 1. Cabinet Power Source Information
Cabinet Style and Power1 | Power Sources | Power Input Receptacles | ||
Distribution Unit |
|
|
| |
|
|
|
| |
Rack Mount Cabinet. AC power | Single phase 120 VAC with neutral | 120 VAC, 60 | Hz NEMA | |
supply (650A integrated power | Single phase 240 VAC with neutral | 240 VAC, 50 | Hz IEC 320 | |
supply) | ||||
|
|
| ||
|
| Japan installations use country | ||
|
| specific receptacles for 100 and | ||
|
| 200 VAC, 50/60 Hz | ||
|
|
|
|
1There is no integrated DC power supply. DC rectifiers can be used if desired; follow manufacturer’s instructions.
Table 2. Circuit Breakers for
Cabinet Type | Circuit Breaker Size |
|
|
Rack Mount Cabinet (120 VAC) 60 Hz | 15 A |
|
|
Rack Mount Cabinet (240 VAC) 50 Hz | 10 A |
|
|
Overview for Avaya IP600 Internet Protocol Communications Server |
|