Chapter 3: Installation

Rackmount Brackets (2)

2M46-04R

HSIM 2

 

HSIM 1

PWR

 

 

CPU

 

 

COM

1

2

Screws (4)

2314-04

Figure 3-3 Installing the Rackmount Brackets

3.With the mounting brackets installed, position the 2M46-04R between the vertical frame members of the 19-inch rack and fasten it securely with mounting screws as shown in Figure 3-4.

19-Inch Rack

2M46-04R

HSIM 2

 

HSIM 1

PWR

 

 

CPU

 

 

COM

1

2

Screws (4)

2314-03

Figure 3-4 Installing the 2M46-04R in a Rack

Bonding the Rackmount Brackets to the 2M46-04RDC

If the 2M46-04RDC is going to be mounted in a rack and needs to meet the GR-1089-CORE Section 9 bonding requirements, use the following instructions to install the 2M46-04RDC into a 19-inch rack.

1.Remove and discard the four cover screws (two from each side) located along the front edges of each side of the 2M46-04RDC.

2.Remove the paint from around the area near the mounting holes on the left and right side of the cover of the 2M46-04RDC. See Figure 3-5.

3.Apply a thin layer of anti-oxidant to the surface where the paint was removed.

3-6

2M46-04R/2M46-04RDC User’s Guide

Page 30
Image 30
Cabletron Systems pmn manual Bonding the Rackmount Brackets to the 2M46-04RDC