Chapter 3 Installing the Cisco ADE 2130 and 2140 Series Appliance

Cisco ADE 2130 and 2140 Series Appliance Power

Warning Before performing any of the following procedures, ensure that power is removed from the DC circuit. Statement 1003

Warning Use copper conductors only. Statement 1025

Warning When stranded wiring is required, use approved wiring terminations, such as closed loop or spade-type with upturned lugs. These terminations should be appropriate size for the wires and should clamp both the insulation and conductor. Statement 1002

Warning Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV) requirements in IEC 60950 based standards. Statement 1033

Warning This product requires short-circuit (overcurrent) protection, to be provided as part of a building installation. Install only in accordance with national and local wiring regulations. Statement 1045

Warning This unit might have more than one power supply connection. All connections must be removed to de-energize the unit. Statement 1028

Note The installation must comply with the 2002 National Electric Code (NEC) and other applicable codes.

Wiring the DC-Input Power Source

Warning Hazardous voltage or energy may be present on DC power terminals. Always replace cover when terminals are not in service. Be sure uninsulated conductors are not accessible when cover is in place. Statement 1075

Warning This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than: 10 A minimum, 60 VDC. Statement 1005

To connect the DC power supply to the Cisco ADE 2130 and 2140 Series appliance:

Step 1 Ensure that the appliance (earth) ground connection has been made by following the instructions in the “Grounding Connections” section on page 3-14.

Warning This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024

Cisco Application Deployment Engine (ADE) 2130 and 2140 Series Appliance Hardware Installation Guide

3-16

78-18579-02

 

 

Page 66
Image 66
Cisco Systems 2130, 2140 manual Wiring the DC-Input Power Source