Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series

Inter Memory

Modbus Reference

Supporting Modbus

Address of Function

of Delta HMI

Address

Function

 

$M200.1

01026

01H, 05H, 0FH

0401H

 

 

 

 

.

 

 

 

.

 

 

 

.

 

 

 

 

 

 

 

$M200.15

01040

01H, 05H, 0FH

040FH

 

 

 

 

$M201.0

01041

01H, 05H, 0FH

0410H

 

 

 

 

.

 

 

 

.

 

 

 

.

 

 

 

 

 

 

 

$M263.0

02033

01H, 05H, 0FH

07F0H

 

 

 

 

.

 

 

 

.

 

 

 

.

 

 

 

 

 

 

 

$M263.15

02048

01H, 05H, 0FH

07FFH

 

 

 

 

For example:

1.Read internal memory $100 of Delta HMI (HMI station number: 1)

: 01 03 00 64 00 01 97 CR LF

Write the value of 1000 into internal memory $100 of Delta HMI (HMI station number: 1)

:01 06 00 64 03 E8 AA CR LF

2.Read internal memory $M100 of Delta HMI (HMI station number: 1)

:01 03 08 34 00 01 BF CR LF

Write the value of 888 into internal memory $M100 of Delta HMI (HMI station number: 1)

:01 06 08 34 03 78 42 CR LF

3.Read internal memory $2000.15 of Delta HMI (HMI station number: 1)

:01 01 00 0F 00 01 EE CR LF

Set internal memory $2000.15 of Delta HMI to ON (HMI station number: 1)

: 01 05 00 0F FF 00 EC CR LF

Set internal memory $2000.15 of Delta HMI to OFF (HMI station number: 1)

:01 05 00 0F 00 00 EB CR LF

4.Read internal memory $M201.0 of Delta HMI (HMI station number: 1)

:01 01 04 10 00 01 E9 CR LF

Set internal memory $M201.0 of Delta HMI to ON (HMI station number: 1)

: 01 05 04 10 FF 00 E7 CR LF

Set internal memory $M201.0 of Delta HMI to OFF (HMI station number: 1)

: 01 05 04 10 00 00 E6 CR LF