Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series
Inter Memory | Modbus Reference | Supporting Modbus | Address of Function | |
of Delta HMI | Address | Function | ||
| ||||
$M200.1 | 01026 | 01H, 05H, 0FH | 0401H | |
|
|
|
| |
. |
|
|
| |
. |
|
|
| |
. |
|
|
| |
|
|
|
| |
$M200.15 | 01040 | 01H, 05H, 0FH | 040FH | |
|
|
|
| |
$M201.0 | 01041 | 01H, 05H, 0FH | 0410H | |
|
|
|
| |
. |
|
|
| |
. |
|
|
| |
. |
|
|
| |
|
|
|
| |
$M263.0 | 02033 | 01H, 05H, 0FH | 07F0H | |
|
|
|
| |
. |
|
|
| |
. |
|
|
| |
. |
|
|
| |
|
|
|
| |
$M263.15 | 02048 | 01H, 05H, 0FH | 07FFH | |
|
|
|
|
For example:
1.Read internal memory $100 of Delta HMI (HMI station number: 1)
: 01 03 00 64 00 01 97 CR LF
Write the value of 1000 into internal memory $100 of Delta HMI (HMI station number: 1)
:01 06 00 64 03 E8 AA CR LF
2.Read internal memory $M100 of Delta HMI (HMI station number: 1)
:01 03 08 34 00 01 BF CR LF
Write the value of 888 into internal memory $M100 of Delta HMI (HMI station number: 1)
:01 06 08 34 03 78 42 CR LF
3.Read internal memory $2000.15 of Delta HMI (HMI station number: 1)
:01 01 00 0F 00 01 EE CR LF
Set internal memory $2000.15 of Delta HMI to ON (HMI station number: 1)
: 01 05 00 0F FF 00 EC CR LF
Set internal memory $2000.15 of Delta HMI to OFF (HMI station number: 1)
:01 05 00 0F 00 00 EB CR LF
4.Read internal memory $M201.0 of Delta HMI (HMI station number: 1)
:01 01 04 10 00 01 E9 CR LF
Set internal memory $M201.0 of Delta HMI to ON (HMI station number: 1)
: 01 05 04 10 FF 00 E7 CR LF
Set internal memory $M201.0 of Delta HMI to OFF (HMI station number: 1)
: 01 05 04 10 00 00 E6 CR LF
Revision January, 2008, Doc. Name: 2007PDD23000007 |