Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007 1-131
Vigor M Series Back to Table
A. HMI factory settings
Baud rate: 19200, 7, EVEN, 1.
Controller station number: 0.
Control area/status area: D0 / D10.
NOTE
1) Controller station number: 0 for PROGRAMMER PORT; 1 for COM PORT
2) VB series also can use this driver.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format Word No. Bit No. Data length
Input Relay Xn n: 0 ~ 770 (Octal) N/A Word (multiple of 8)
Output Relay Yn n: 0 ~ 770 (Octal) N/A Word (multiple of 8)
Auxiliary Relay Mn n: 0 ~ 5112 N/A Word (multiple of 8)
Special Relay Mn n: 9000 ~ 9248 N/A Word (9000 + multiple
of 8)
Step Relay Sn n: 0 ~ 992 N/A Word (multiple of 8)
Timer Present Value Tn n: 0 ~ 255 N/A Word
16-bit Counter Present Value Cn n: 0 ~ 199 N/A Word
32-bit Counter Present Value Cn n: 200 ~ 255 N/A Word
Data Register Dn n: 0 ~ 8191 N/A Word
Special Data Register Dn n: 9000 ~ 9248 N/A Word
Contacts
Read/Write range
Contact type Format Word No. Bit No.
Input Relay Xn N/A n: 0 ~ 777(Octal)
Output Relay Yn N/A n: 0 ~ 777(Octal)
Auxiliary Relay Mn N/A n: 0 ~ 5119
Special Relay Mn N/A n: 9000 ~ 9255
Step Relay Sn N/A n: 0 ~ 999
Timer Contact Tn N/A n: 0 ~ 255
Counter Contact Cn N/A n: 0 ~ 255
Timer Coil TCn N/A n: 0 ~ 255
Counter Coil CCn N/A n: 0 ~ 255