Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007 1-71
Mirle FAMA SC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller station number: 0.
Control area/status area: 40100 / 40200.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format Word No. Bit No. Data Length
Output Registers Wn n: 40001 ~ 50000 N/A Word
Input Registers Wn n: 30001 ~ 40000 N/A Word
¾ Input Registers is “read only”.
Contacts
Read/Write Range
Contact type Format Word No. Bit No.
Discrete Outputs Bn N/A n: 1 ~ 10000
Discrete Inputs Bn N/A n: 10001 ~ 20000
¾ Discrete Inputs is “read only”.
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male
(RS-232)
Controller
9 pin D-SUB male
(RS-232)
Controller
9 pin D-SUB male
(RS-232)
RXD (2) (3) TXDTXD (3)GND (5)(2) RXD(5) SG
Top View
Pin1