Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series
YOKOGAWA ACE PLC | Back to Table |
A. HMI factory settings
Baud rate: 9600, 8, EVEN, 1. (ASCII code)
Controller station number: 1.
CPU NO. : 1.
Control area/status area: D1 / D10.
NOTE
1)CheckSum and End character (CR, LF) are not used during communication. Therefore, the controller should be set to “Not using CheckSum and End character”.
2)CPU number is used during communication, however, Screen Editor software does not have this selection. Therefore, if the user desires to set CPU number, please set HMI station number in “General” tab in the ”Configuration” dialog box in “Options” menu (Options Æ ”Configuration” Æ General). (HMI station number is regarded as CPU number. The default setting of HMI station number is 0, but 0 is an illegal number, the user must set it as a legal value.
B. Definition of controller Read/Write address
Registers
Register Type | Format |
|
| Word No. | Data Size |
WORD_DEVICE_X | Xn | n: 201 ~ 65464 | Word | ||
WORD_DEVICE_Y | Yn | n: 201 ~ 65464 | Word | ||
WORD_DEVICE_I | In | n: 1 ~ | 16384 | Word | |
WORD_DEVICE_E | En | n: 1 ~ | 4096 | Word | |
WORD_DEVICE_L | Ln | n: 1 ~ | 65488 | Word | |
WORD_DEVICE_M | Mn | n: 1 ~ | 9984 | Word | |
WORD_DEVICE_TP | TPn | n: 1 ~ | 3072 | Word | |
|
|
|
|
| |
WORD_DEVICE_CP | CPn | n: 1 ~ | 3072 | Word | |
|
|
|
|
| |
WORD_DEVICE_D | Dn | n: 1 ~ | 8192 | Word | |
|
|
|
|
| |
WORD_DEVICE_B | Bn | n: 1 ~ | 32768 | Word | |
|
|
|
|
| |
WORD_DEVICE_W | Wn | n: 1 ~ | 65499 | Word | |
|
|
|
|
| |
WORD_DEVICE_Z | Zn | n: 1 ~ | 512 | Word | |
|
|
|
|
|
|
WORD_DEVICE_V | Vn | n: 1 | ~ | 64 | Word |
|
|
|
|
|
|
WORD_DEVICE_R | Rn | n: 1 | ~ | 4096 | Word |
|
|
|
|
|
|
WORD_DEVICE_TS | TSn | n: 1 | ~ | 3072 | Word |
|
|
|
|
|
|
WORD_DEVICE_CS | CSn | n: 1 | ~ | 3072 | Word |
|
|
|
|
|
|
¾WORD_DEVICE_X / WORD_DEVICE_Y: The last two digits of address must be 1 or the multiple of 16+1 and less than 65.
Revision January, 2008, Doc. Name: 2007PDD23000007 |