Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series
Modicon TSX Micro | Back to Table |
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller station number: 2.
Control area/status area: %MW0 / %MW10.
NOTE
1)HMI station needs to be adjusted to 1 ~ 8.
2)PLC station and HMI station can be the same.
3)The internal memory and relative parameters in PLC should be set properly first. Otherwise, it cannot communicate except %S.
B. Definition of controller Read/Write address
Registers
Register Type | Format | Word No. | |
WORD_DEVICE_ Internal | %MWn | n: 0 | ~ 65534 |
|
|
|
|
WORD_DEVICE_ System | %SWn | n: 0 | ~ 127 |
|
|
|
|
WORD_DEVICE_ Input | %KWn | n: 0 | ~ 65534 |
|
|
|
|
¾ %KWn is “read only”. |
|
|
|
Contacts |
|
|
|
Bit No. N/A N/A N/A
Data Size
Word
Word
Word
Contact type | Format | Word No. | Bit No. |
BIT_DEVICE_ Internal | %Mn:b | n:0 ~ 65534 | b:0 ~ 15 |
|
|
|
|
BIT_DEVICE_ System | %Sn | - | n:0 ~ 127 |
|
|
|
|
BIT_DEVICE_ Internal1 | %Mn | - | n:0 ~ 65534 |
|
|
|
|
¾%Mn: b is Bit address that corresponds to WORD_DEVICE_ Internal (%MWn).
¾%Mn is PLC internal relay address.
¾The read/write range of WORD_DEVICE_ Internal / BIT_DEVICE_ Internal depends on PLC used memory.
Revision January, 2008, Doc. Name: 2007PDD23000007 |