Delta DOP Series HMI Connection ManualDOP-A/AE/AS  Series
| Mitsubishi A Series AJ71UC24 Communication Module | Back to Table | 
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller Station number: 0.
Control area/status area: D0 / D10.



 NOTE
NOTE
1)This driver utilizes CheckSum.
2)Please set “PLC Mode” switch to position 5.
3)If OUTPUT Relay (Y) and Special Data Relay (SM) are set to 1, PLC will stop communication and the communication will not recover automatically. PLC will need to be manually reset.
B. Definition of controller Read/Write address
Registers
| Register Type | Format | 
 | Read/Write Range | Data length | ||
| Word No. | Bit No. | |||||
| 
 | 
 | 
 | ||||
| Input | Xn | n: 0 ~ 7FF | N/A | Word (multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Output | Yn | n: 0 ~ 7FF | N/A | Word (multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Link Relay | Bn | n: 0 ~ FFF | N/A | Word (multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Internal Relay | Mn | n: 0 ~ 8191 | N/A | Word (multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Special Internal Relay | SMn | n: 9000 ~ 9255 | N/A | Word (9000 + multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Latch Relay | Ln | n: 0 ~ 2047 | N/A | Word (multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Annunciator | Fn | n: 0 ~ 2047 | N/A | Word (multiple of 16) | ||
| 
 | 
 | 
 | 
 | 
 | ||
| Timer Value | TNn | n: 0 ~ 999 | N/A | Word | ||
| 
 | 
 | 
 | 
 | 
 | 
 | |
| Counter Value | CNn | n: 0 | ~ 999 | N/A | Word | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| Data Register | Dn | n: 0 | ~ 8191 | N/A | Word | |
| 
 | 
 | 
 | 
 | 
 | ||
| Special Data Register | SDn | n: 9000 ~ 9255 | N/A | Word | ||
| 
 | 
 | 
 | 
 | 
 | 
 | |
| File Register | Rn | n: 0 | ~ 8191 | N/A | Word | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| Link Register | Wn | n: 0 | ~ FFF | N/A | Word | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| Revision January, 2008, Doc. Name: 2007PDD23000007 | 