Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series

Mitsubishi A Series AJ71UC24 Communication Module

Back to Table

A. HMI factory settings

Baud rate: 9600, 8, ODD, 1.

Controller Station number: 0.

Control area/status area: D0 / D10.

NOTE

1)This driver utilizes CheckSum.

2)Please set “PLC Mode” switch to position 5.

3)If OUTPUT Relay (Y) and Special Data Relay (SM) are set to 1, PLC will stop communication and the communication will not recover automatically. PLC will need to be manually reset.

B. Definition of controller Read/Write address

Registers

Register Type

Format

 

Read/Write Range

Data length

Word No.

Bit No.

 

 

 

Input

Xn

n: 0 ~ 7FF

N/A

Word (multiple of 16)

 

 

 

 

 

Output

Yn

n: 0 ~ 7FF

N/A

Word (multiple of 16)

 

 

 

 

 

Link Relay

Bn

n: 0 ~ FFF

N/A

Word (multiple of 16)

 

 

 

 

 

Internal Relay

Mn

n: 0 ~ 8191

N/A

Word (multiple of 16)

 

 

 

 

 

Special Internal Relay

SMn

n: 9000 ~ 9255

N/A

Word (9000 + multiple of 16)

 

 

 

 

 

Latch Relay

Ln

n: 0 ~ 2047

N/A

Word (multiple of 16)

 

 

 

 

 

Annunciator

Fn

n: 0 ~ 2047

N/A

Word (multiple of 16)

 

 

 

 

 

Timer Value

TNn

n: 0 ~ 999

N/A

Word

 

 

 

 

 

 

Counter Value

CNn

n: 0

~ 999

N/A

Word

 

 

 

 

 

 

Data Register

Dn

n: 0

~ 8191

N/A

Word

 

 

 

 

 

Special Data Register

SDn

n: 9000 ~ 9255

N/A

Word

 

 

 

 

 

 

File Register

Rn

n: 0

~ 8191

N/A

Word

 

 

 

 

 

 

Link Register

Wn

n: 0

~ FFF

N/A

Word

 

 

 

 

 

 

1-76

Revision January, 2008, Doc. Name: 2007PDD23000007