Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series

Jetter Nano Series PLC

Back to Table

A. HMI factory settings

Baud rate: 9600, 8, EVEN, 1 (RS-232).

Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.)

Control area/status area: WR0 / WR10.

NOTE

1)Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.

2)Only 1 Bit or 1 Word can be transferred for each communication.

3)In general, each register occupies max. 24 Bits. However, some registers occupies 8 Bits only.

4)Because the initial time of this controller is longer, it is recommended to set HMI startup delay time (Recommended time is 10 seconds).

5)When the register R is used for Double Word device, please set its format as signed format. (The default format in Screen Editor is signed format)

B. Definition of controller Read/Write address

Registers

Register Type

Format

 

Read/Write Range

 

 

 

Word No.

 

Bit No.

 

 

 

 

 

 

16 Bits Register

WRn

n:

0 ~ 32767

 

N/A

 

 

 

 

 

 

32 Bits Register

Rn

n:

0 ~ 32767

 

N/A

 

 

 

 

 

 

 

Data

Length

16Bits

24Bits

Only the first 16 bits are used for WRn registers.

Only the first 24 bits are used for Rn registers, the highest 8 bits (Bit 24 ~ 31) are set to 0 by default setting.

(24-bit Integer : If in decimal format, the range is -8388608 ~ +8388607. If in hexadecimal format, the range is 0x000000 ~ 0xFFFFFF.)

NOTE

1) The difference between WRn and Rn:

yWhen using devices that the data length is in Word, only Bit 0 ~ 15 are valid for both of WRn and Rn registers.

yWhen using devices that the data length is in Double Word,

if the read/write address format is set to WRn, the Bit 0 ~ 15 of WRn register is the low word of a read/write value, the Bit 0 ~ 15 of WRn+1 register is the high word of a read/write value.

1-40

Revision January, 2008, Doc. Name: 2007PDD23000007

Page 41
Image 41
Delta Electronics DOP-A/AE/AS manual Jetter Nano Series PLC