Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series
Jetter Nano Series PLC | Back to Table |
A. HMI factory settings
Baud rate: 9600, 8, EVEN, 1
Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.)
Control area/status area: WR0 / WR10.
NOTE
1)Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.
2)Only 1 Bit or 1 Word can be transferred for each communication.
3)In general, each register occupies max. 24 Bits. However, some registers occupies 8 Bits only.
4)Because the initial time of this controller is longer, it is recommended to set HMI startup delay time (Recommended time is 10 seconds).
5)When the register R is used for Double Word device, please set its format as signed format. (The default format in Screen Editor is signed format)
B. Definition of controller Read/Write address
Registers
Register Type | Format |
| Read/Write Range |
|
| |
| Word No. |
| Bit No. |
| ||
|
|
|
|
| ||
16 Bits Register | WRn | n: | 0 ~ 32767 |
| N/A | |
|
|
|
|
|
| |
32 Bits Register | Rn | n: | 0 ~ 32767 |
| N/A | |
|
|
|
|
|
|
|
Data
Length
16Bits
24Bits
Only the first 16 bits are used for WRn registers.
Only the first 24 bits are used for Rn registers, the highest 8 bits (Bit 24 ~ 31) are set to 0 by default setting.
NOTE
1) The difference between WRn and Rn:
yWhen using devices that the data length is in Word, only Bit 0 ~ 15 are valid for both of WRn and Rn registers.
yWhen using devices that the data length is in Double Word,
if the read/write address format is set to WRn, the Bit 0 ~ 15 of WRn register is the low word of a read/write value, the Bit 0 ~ 15 of WRn+1 register is the high word of a read/write value.
Revision January, 2008, Doc. Name: 2007PDD23000007 |