Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series
Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH | Back to Table |
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.)
Control area/status area: D0 / D10.
NOTE
1)This driver supports all Mitsubishi A series CPU port. Mitsubishi A series CPU port can be divided into the following five categories according the used CPU code (used during communication):
yA0J2…
yA1N…
yA1S ( / A2S / A2N …)
yA3N ( / A1SH / A2SH …)
yA2A ( / A2AS / A2USH …)
Delta HMI can support A2USH CPU port (same as A2A, A2AS CPU port.) and A1SH CPU port (same as A3N, A2ASH CPU port.).
2)L and M: The communication address of L is the same as communication address of M.
3)PX and X:
In Mitsubishi A2A PLC, the communication address of PX and X are the same.
In other Mitsubishi A series PLCs, X is from odd address and PX is from even address. That is one place where PX and X differ.
4)X, Y, B, M, SM, L, F, PX
When PLC station number is set to 255, only the value of even addresses will be read/written.
When PLC station number is set to other number (not 255), all value of all addresses will be read/written.
5)R address: R address will be different according to the size of File Register responded from PLC.
For example, A2USH: | 1K: 3800 ~ 4000H | |
| 2K: 3000 ~ 4000H | |
| 3K: 2800 | ~ 4000H |
| 4K: 2000 | ~ 4000H |
| 5K: 4000 | ~ 6800H(cy) |
| 6K: 4000 | ~ 7000H(cy) |
File Register: PLC must be started correctly or the read / write value will be incorrect.
Revision January, 2008, Doc. Name: 2007PDD23000007 |