Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series
Mitsubishi FX/FX2N PLC | Back to Table |
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.)
Control area/status area: D0 / D10.
NOTE
1)If connecting to Mitsubishi FXxN series PLC, the user can use both FX2N and FX series communication protocol.
2)If connecting to Mitsubishi FX series PLC, the user can only use FX series communication protocol.
3)Some registers of Mitsubishi PLCs are “read only”, however, when you write these “read only” registers, PLCs will not report any communication error to HMI and this will cause HMI errors. Please be aware of this when editing PLC program (this normally occurs when using FX series protocol when connecting to a FXxN series PLC).
4)If connecting to Mitsubishi FXxN series PLC, it is recommended for the user to use FX2N protocol.
B. Definition of controller Read/Write address
Registers
Register Type |
| Format |
|
| Read/Write Range | ||
|
| Word No. | Bit No. |
| |||
|
|
|
|
| |||
Auxiliary Relay | Mn |
| n: 0 ~ | 3064 | N/A | ||
|
|
|
|
| |||
Special Auxiliary Relay | Mn |
| n: 8000 ~ 8248 | N/A | |||
|
|
|
|
|
| ||
Status Relay | Sn |
| n: 0 ~ | 992 | N/A | ||
|
|
|
|
|
| ||
Input Relay | Xn |
| n: 0 ~ | 360(octal) | N/A | ||
|
|
|
|
|
|
| |
Output Relay | Yn |
| n: 0 | ~ | 360(octal) | N/A | |
|
|
|
|
|
|
| |
Timer PV | Tn |
| n: 0 | ~ | 255 | N/A | |
|
|
|
|
|
| ||
Cn |
| n: 0 ~ | 199 | N/A | |||
|
|
|
|
| |||
Cn |
| n: 200 ~ 255 | N/A | ||||
|
|
|
|
|
|
| |
Data Register | Dn |
| n: 0 | ~ | 7999 | N/A | |
|
|
|
|
| |||
Special Data Register | Dn |
| n: 8000 ~ 8255 | N/A | |||
|
|
|
|
|
|
|
|
Data length
Byte
Byte
Byte
Byte
Byte
Word
Word
Double Word
Word
Word
¾Auxiliary Relay/ Special Auxiliary Relay/ Status Relay/ Input Relay /Output Relay: Address must be the multiple of 8.