Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series

¾CJ1M Models: An: A0-A477 is “read only”.

Contacts

Contact type

Format

 

Read/Write Range

 

Word No.

Bit No.

 

 

 

CIO area

CIOBnbb

n: 0 ~ 9999

bb: 00 ~ 15

 

 

 

 

Hold area

HBnbb

n: 0 ~ 999

bb: 00 ~ 15

 

 

 

 

Auxiliary area

ABnbb

n: 0 ~ 999

bb: 00 ~ 15

 

 

 

 

DM area

DBnbb

n: 0 ~ 65535

bb: 00 ~ 15

 

 

 

 

EM area

EBm.nbb

n: 0 ~ 65535

 

 

 

m: 0 ~ 12 (bank no.)

bb: 00 ~ 15

 

 

 

 

 

Timer area

TBn

N/A

 

n: 0 ~ 9999

 

 

 

 

 

Counter area

CBn

N/A

 

n: 0 ~ 9999

 

 

 

 

Work area

WBnbb

n: 0 ~ 999

bb: 00 ~ 15

 

 

 

 

EM Current Bank area

EMBnbb

n: 0 ~ 65535

bb: 00 ~ 15

 

 

 

 

Index Register

IRBnbb

n: 0 ~ 99

bb: 00 ~ 31

 

 

 

 

 

DR area

DRBnbb

n: 0

~ 99

bb: 00 ~ 15

 

 

 

 

 

TK area

TKBnbb

n: 0

~ 1022 (Even

bb: 00 ~ 15

 

 

No.)

 

NOTE

1) The following address cannot be written:

yIRn and DRn: It is not valid if the users write them. HMI will not show any error message if the write operation is done.

yAn and Abnbb: Some range of An and Abnbb (Auxiliary area) is “read only”.

yTKn / TKBnbb / TBn / CBn / EMBnbb / IRBnbb / DRBnbb: Writing these addresses is not allowed. If the write operation is done, the error will occur and display the error message “Command Can Not be Executed…” on the screen of HMI.

2)The unit of IR address is “Double Word”.

3)The unit of TK address is “Byte” and it should be even number.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-117

Page 118
Image 118
Delta Electronics DOP-A/AE/AS manual ¾ CJ1M Models An A0-A477 is read only