Delta Electronics DOP-A/AE/AS manual Siemens S7 200 PLCBack to Table A. HMI factory settings

Models: DOP-A/AE/AS

1 137
Download 137 pages 41.7 Kb
Page 121
Image 121

Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series

Siemens S7 200 PLCBack to Table A. HMI factory settings

Baud rate: 9600, 8, EVEN, 1.

Controller station number: 2.

Control area/status area: VW0 / VW10.

B. Definition of controller Read/Write address

Register

 

Register Type

Format

 

Read/Write Range

 

 

 

Word No.

 

Bit No.

 

 

 

 

 

 

 

 

Timer

Tn

 

n: 0 ~ 255

 

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input Word

AIWn

 

n: 0 ~ 30

 

N/A

 

 

 

 

 

 

 

 

 

 

Counter

Cn

 

n: 0 ~ 255

 

N/A

 

 

 

 

 

 

 

 

 

 

Analog Output Word

AQWn

 

n: 0 ~ 30

 

N/A

 

 

 

 

 

 

 

 

 

 

Input Image

IWn

 

n: 0 ~ 14

 

N/A

 

 

 

 

 

 

 

 

 

 

Input Image

IDn

 

n: 0 ~ 12

 

N/A

 

 

 

 

 

 

 

 

 

 

Output Image

QWn

 

n: 0 ~ 14

 

N/A

 

 

 

 

 

 

 

 

 

 

Output Image

QDn

 

n: 0 ~ 12

 

N/A

 

 

 

 

 

 

 

 

 

 

Special Bits

SMWn

 

n: 0 ~ 199

 

N/A

 

 

 

 

 

 

 

 

 

 

Special Bits

SMDn

 

n: 0 ~ 197

 

N/A

 

 

 

 

 

 

 

 

 

 

Internal Bits

MWn

 

n: 0 ~ 98

 

N/A

 

 

 

 

 

 

 

 

 

 

Internal Bits

MDn

 

n: 0 ~ 96

 

N/A

 

 

 

 

 

 

 

 

 

 

Data Area

VWn

 

n: 0 ~ 9998

 

N/A

 

 

 

(DBWn)

 

(n: 0 ~ 9998)

 

 

 

 

 

 

 

 

 

 

 

 

Data Area

VDn

 

n: 0 ~ 9996

 

N/A

 

 

 

 

 

 

 

 

 

 

Special S

SWn

 

n: 0 ~ 99

 

N/A

 

 

 

 

 

 

 

 

 

 

Special S

SDn

 

n: 0 ~ 97

 

N/A

 

 

 

 

 

 

 

 

Contacts

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact type

Format

 

Read/Write Range

 

 

 

Word No.

 

Bit No.

 

 

 

 

 

 

 

 

Timer Bit

Tn

N/A

 

n: 0 ~ 255

 

 

 

 

 

 

 

 

 

Counter Bit

Cn

N/A

 

n: 0 ~ 255

 

 

 

 

 

 

 

 

 

Input Image

In.b

n: 0 ~ 15

 

b: 0 ~ 7

 

 

 

 

 

 

 

 

 

Output Image

Qn.b

n: 0 ~ 15

 

b: 0 ~ 7

 

 

 

 

 

 

 

 

 

Special Bit

SMn.b

n: 0 ~ 200

 

b: 0 ~ 7

 

 

 

 

 

 

 

 

 

Internal Bit

Mn.b

n: 0 ~ 99

 

b: 0 ~ 7

 

 

 

 

 

 

 

 

 

Data Area Bit

Vn.b

n: 0 ~ 9999

 

b: 0 ~ 7

 

 

 

 

 

 

 

 

1-120

 

 