Delta DOP Series HMI Connection ManualDOP-A/AE/AS Series

1.1Pin Definition of Serial Communication

„ DOP-A Series

 

 

 

 

 

 

 

COM1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIN

Mode

 

 

 

 

 

 

 

RS-232

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

N.C

 

 

 

 

Pin1

 

2

RXD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

TXD

 

 

 

 

 

 

 

4

N.C

 

 

 

 

 

 

 

5

GND

 

 

 

 

 

 

 

6

N.C

 

 

 

 

 

 

 

7

RTS

 

 

 

 

 

 

 

8

CTS

 

 

 

 

 

 

 

9

N.C

 

COM2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIN

 

Mode 1

Mode 2

 

Mode 3

 

 

 

 

RS-232

RS-422

 

RS-485

 

 

 

 

 

 

 

 

 

1

 

N.C

RXD-

 

D-

 

 

Pin1

2

 

RXD

RXD+

 

D+

 

 

 

3

 

TXD

TXD+

 

D+

 

 

 

4

 

N.C

TXD-

 

D-

 

 

 

5

 

GND

GND

 

GND

 

 

 

6

 

N.C

RTS-

 

N.C

 

 

 

7

 

RTS

RTS+

 

N.C

 

 

 

8

 

CTS

CTS+

 

N.C

 

 

 

9

 

N.C

CTS-

 

N.C

 

 

 

 

 

 

 

 

 

 

NOTE

1)Mode 3 is for RS-485. Pin 2 & 3 are D+ and pin 1 & 4 are D-.

2)Grounding is highly recommended if RS-485 & RS-422 are used for long transmission.

3)DO NOT connect Frame Ground (FGND) to GND. Please connect FGND to the outer covering of connector.

4)Transmission speed is relevant to distance and baud rate.

Revision January, 2008, Doc. Name: 2007PDD23000007