Read/write image data
For more information visit: www.EatonElectrical.comMN05013001E 117
Attention!
The function blocks and DW markers (32-bit values) of
EZ800/EZD operate with signed values.
Applies to
MD, MW,
MB, M
Left = Most
significant bit, byte,
word
Right = Least
significant bit, byte,
word
32 bit MD1
16 bit MW2 MW1
8 bit MB4 MB3 MB2 MB1
1 bit M32 to M25 M24 to M17 M16 to M9 M8 to M1
32 bit MD2
16 bit MW4 MW3
8 bit MB8 MB7 MB6 MB5
1 bit M64 to M57 M56 to M49 M48 to M41 M40 to M33
JThe relevant marker values are transferred in Intel format.
In other words, the first byte is the low byte (Byte 5) and the
last byte the high byte.
The latest editions of these manuals are available as PDF files
from the Internet at: www.EatonElectrical.com. EZ800 manual
search term: MN05013004E. EZD manual search term:
MN05013005E.