Data exchange procedure

J

In order to use input/output data and control commands simultaneously:

Only after the “Control commands” data exchange has been completed, will the I/O data be refreshed.

All specified commands and parameters must be transferred in hexadecimal format.

J

The following tables show the different control commands possible. These essential control commands fall into three essential categories – real-time clock, image and function blocks.

Please also note the relevant description of the real-time clock provided in the EZ500/700 manual (MN05013003E).

Telegram structure

Byte

Meaning

Value (hex), sent by

 

 

Master

 

Slave

 

 

 

 

 

0

 

Toggle byte

 

J page 44

 

 

1

 

Command

 

 

 

 

 

 

 

Read

 

93

 

 

 

 

Write

 

B3

 

 

 

 

 

 

 

 

 

 

Response

 

 

 

 

 

 

Read successful

 

 

 

 

 

 

 

C2

 

 

 

 

 

 

 

 

 

 

 

Write successful

 

 

C1

 

 

 

Command rejected

 

 

C0

 

 

 

 

 

 

 

2

 

Len

05

 

05

 

 

 

 

 

 

 

3

 

Index

 

0 – 21

 

0 – 21

4 – 8

 

Data 1 – 4

depending on index,

 

 

 

 

 

J Table 6

 

 

 

 

 

 

 

 

 

 

1)0 = Time/date, J Table 6

1 = Summer time, J Table 7

2 = Winter time, J Table 8

MN05013001E

For more information visit: www.EatonElectrical.com