EZ800/EZD Control Commands

 

 

Table 81:

Operand overview

 

 

 

 

 

 

 

 

 

 

 

 

Index

Operand

 

 

Read

 

Write

(hex)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

Bit IO, J Table 82

 

×

 

 

01

 

Mode, J Table 83

 

 

×

 

 

 

 

 

 

 

 

 

 

02

 

Setpoint: –32768 to +32767

I1

 

×

 

c1

03

 

Actual value: –32768 to +32767

I2

 

×

 

c1

04

 

Proportional gain

KP

×

 

c1

 

 

[%], Value range: 0 to 65535

 

 

 

 

 

05

06

07

Reset time [0.1 s], Value range: 0 to 65535

TN

 

×

 

c1

Rate time [0.1 s], Value range: 0 to 65535

TV

 

×

 

c1

Scan time = Time between function block calls.

TC

×

 

c1

Value range: 0.1s to 6553.5s.

 

 

 

 

 

If 0 is entered as the value, the scan time will be determined

 

 

 

 

 

by the program cycle time.

 

 

 

 

 

08

 

Manual manipulated variable, value range: –4096 to +4095

MV

 

×

 

c1

09

 

Manipulated variable

QV

×

 

 

Mode: UNI, value range: 0 to +4095 (12 bit)

Mode: BIP, value range: –4096 to +4095 (13 bit)

1)The value can only be written if it is assigned to a constant in the program.

J

The data for index 2 and 9 is transferred as a 32-bit value in Intel format (Data 1 – Low Byte .. Data 2 - High Byte).