Read/write function block data
Table 34: Index 00 – Parameters
Meaning | Bit | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Appears in the parameter menu |
|
|
|
|
|
|
|
|
|
Yes/no |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0/1 | |
Timer mode |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0 | 0 | 0 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0 | 0 | 1 |
| |
|
|
|
|
| 0 | 1 | 0 |
| |
|
|
|
|
| 0 | 1 | 1 |
| |
On and off delayed |
|
|
|
|
| 1 | 0 | 0 |
|
(two time setpoints) |
|
|
|
|
|
|
|
|
|
On and off delayed each with random setpoint (two time |
|
|
|
|
| 1 | 0 | 1 |
|
setpoints) |
|
|
|
|
|
|
|
|
|
Impulse transmitter |
|
|
|
|
| 1 | 1 | 0 |
|
|
|
|
|
|
|
|
|
|
|
Flashing relay (two time setpoints) |
|
|
|
|
| 1 | 1 | 1 |
|
Time base |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FB not used |
|
|
| 0 | 0 |
|
|
|
|
Millisecond: S |
|
|
| 0 | 1 |
|
|
|
|
Second: M:S |
|
|
| 1 | 0 |
|
|
|
|
Minute: H:M |
|
|
| 1 | 1 |
|
|
|
|
Use as constant and therefore can be written to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Time setpoint S1 |
|
| 0/1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Time setpoint S2 |
| 0/1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Example:
Data 1 (Byte 5) = 0xAC
Meaning:
The values appear in the Parameter menu. The time is used in the impulse transmitter mode with the Second time base. The time setpoint S1 is assigned a constant and the time setpoint S2 is assigned a variable such as I7, I8 C2...etc.