For more information visit: www.EatonElectrical.com
Appendix
MN05013001E188
Ambient mechanical conditionsElectromagnetic compatibility (EMC)
Pollution degree 2
Degree of protection EN 50178
IEC 60529 VBG4 IP20
Oscillations IEC 60068-2-6 10 to 57 Hz (constant
amplitude 0.15 mm)
57 to 150 Hz (constant
acceleration 2 g)
Shocks IEC 60068-2-27 18 shocks
(semi-sinusoidal 15 g/11 ms)
Drop IEC 60068-2-31 Drop height 50 mm
Free fall, packaged IEC 60068-2-32 1 m
Electrostatic discharge IEC/EN 61000-4-2, degree of
severity 3 8 kV air discharge,
6 kV contact discharge
Electromagnetic fields IEC/EN 61 000-4-3 Field strength 10 V/m
Radio interference suppression EN 55011, EN 55022 Limit class A
Burst IEC/EN 61000-4-4, degree of
severity 3 2 kV supply lines, 1kV signal
lines
High-energy pulses (surge)
EZ...-DC... IEC/EN 61000-4-5, degree of
severity 2 0.5 kV power cable
symmetrical
Line-conducted interference IEC/EN 61000-4-6 10 V