Technical Data
For more information visit: www.EatonElectrical.comMN05013001E 187

Technical Data General

Ambient temperatures

Standards and regulations EN55011, EN 55022,
IEC/EN61-4, IEC 60068-2-27,
IEC61158
Dimensions (W × H × D) 35.5 × 90 × 56.5 mm
Weight 150 g
Mounting Top-hat rail to DIN 50022, 35 mm
Screw fixing with fixing brackets
EZB4-101-GF1 (accessories)
Ambient temperature
Installed horizontally/vertically Cold to IEC 60068-2-1
Heat to IEC 60068-2-2 –25 to 55 °C
Condensation Prevent condensation with
suitable measures
Storage/transport temperature –40 to +70 °C
Relative air humidity IEC 60068-2-30 5 to 95 %, non-condensing
Air pressure (operation) 795 to 1080 hPa
Corrosion resistance IEC 60068-2-42
IEC 60068-2-43 SO2 10 cm3/m3, 4 days
H2S 1 cm3/m3, 4 days