Read/write image data

Text function blocks: D1 – D16

The following commands are used to read the logic state of the individual text function blocks (D markers).

Telegram structure

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

J page 44

 

 

 

 

 

 

 

 

 

 

1

 

Command: Read

 

88

 

 

 

Response:

 

 

 

 

 

 

 

Read successful

 

C2

 

 

 

 

 

 

 

 

 

 

 

Command

 

C01

 

 

 

rejected

 

 

 

 

2

 

Len

 

01

 

01

3

 

Type

 

94

 

94

 

 

 

 

 

 

 

4

 

Index

00

 

00

 

 

 

 

 

 

 

5

 

Data 1 (Low Byte)

00

 

J Table 12

 

 

 

 

 

 

 

6

 

Data 2 (High Byte)

 

00

 

J Table 12

7 – 8

 

Data 3 – 4

 

00

 

00

 

 

 

 

 

 

 

 

1)Possible causes J page 91 Table 12: Byte 5 to 6: Data 1 to 2

Data 1

Bit 7 6 5 4 3 2 1 0

 

 

D1

0/1

 

 

D2

0/1

 

 

...

...

 

 

D8

0/1

Data 2

Bit 7 6 5 4 3 2 1 0

 

 

D9

0/1

 

 

D10

0/1

 

 

...

...

 

 

D16

0/1

 

 