Inputs/Outputs, EZ700/800/EZD Operating Mode

“Outputs 1 byte” module: R1 – R8

J

When this module is selected, the master only sends 1 byte (coil output data S1 to S8) via PROFIBUS.

Byte

Meaning

Value

0

Status of R1 to R8

J Table 5 on Page 41

 

 

 

Requirement:

The “Outputs; 1 byte” module must have been selected.

The input data and control commands can now only be used if you have selected the appropriate modules as well.

Note on using the 1 byte modules

The 1 byte modules are not available in all device combinations. If any problems occur in handling, first check the state of the GW message in the status display of the basic unit:

GW static:

The 1-byte mode can be used

GW flashing:

Check the device version of the EZ204-

 

DP and the basic unit. If these are valid,

 

check the configuration in the PROFIBUS

 

network and the Configurator.