EZ800/EZD Control Commands
Example 1
Read marker bit M62
Byte |
| Meaning | Value (hex), sent by | |||
|
|
|
| Master |
| Slave |
0 |
| Toggle byte |
| 81 |
| 80 |
1 |
| Command: Read |
| 91 |
| – |
|
| Response: Read |
| – |
| C2 |
|
| successful |
|
|
|
|
2 |
| Len |
| 01 |
| 01 |
3 |
| Type |
| 0B |
| 0B |
4 |
| Index |
| 3E |
| 3E |
5 |
| Data 1 |
| 00 |
| 01 |
|
|
|
|
|
|
|
6 |
| Data 2 | 00 |
| 00 | |
|
|
|
|
|
|
|
7 |
| Data 3 | 00 |
| 00 | |
|
|
|
|
|
|
|
8 |
| Data 4 | 00 |
| 00 | |
|
|
|
|
|
|
|
Result: Data 1 = 01hex J M62 was set
118 | For more information visit: www.EatonElectrical.com | MN05013001E |