Read/write image data

Read/write image data

J

Please also observe the relevant description of possible image data provided in the EZ500/700 manual (MN05013003E) or in the EZSoft Help.

The latest edition of the manual is available as a PDF file from the Internet at: www.EatonElectrical.com. Search Term: MN05013003E.

General notes on working with image data

Write outputs

System time

Read inputs

Image data

Image data

written

written

EZ/EZD

 

 

Program cycle

EZ-LINK

(0 ... 20 ms)

 

Interrupt function

 

(every 12 or 25 ms)

When writing to image data, it must be remembered that an image (e.g. inputs, outputs,... ) used in the EZ700/EZ800/EZD program is also written cyclically by the actual program. The only image data that is unchanged is the data that is not used in the program and is therefore not overwritten in the program cycle. This operating principle also means that an image written via EZ-LINK, such as output data is only then output at the physical outputs of the EZ700/EZ800/EZD when the control relay is in Run mode.

MN05013001E

For more information visit: www.EatonElectrical.com