Read/write function block data

Operating hours counters: O1 – O4

Telegram structure

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

 

J page 44

 

 

1

 

Command:

 

 

 

 

 

 

 

Read

89

 

 

 

 

 

 

 

 

 

 

 

 

Write

8D

 

 

 

 

 

 

 

 

 

 

Response:

 

 

 

 

 

 

Read successful

 

 

C2

 

 

 

Write successful

 

 

C1

 

 

 

Command rejected

 

 

C01

2

 

Type

92

 

92

3

 

Instance2

 

00 – 03

 

00 – 03

4

 

Index

 

J Table 30

 

 

5 – 8

 

Data 1 – 4

 

depending on index, J Table 31

 

 

 

 

 

 

 

 

1)Possible causes J page 91

2)EZ provides 4 operating hours counters O1 to O4. These can be addressed using the instance (0 – 3).

Table 30: Operand overview

Index

Operand

 

 

 

Read

 

Write

(hex)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

Parameters J Table 31

 

 

 

×

 

 

01

 

Control byte J Table 32

 

 

 

×

 

 

02

 

Actual value

 

S12

 

×

 

c1

03

 

Counter setpoint 2

 

S22

 

×

 

c1

1)The value can only be written if it is assigned to a constant in the program.

2)A 32-bit value is transferred in data bytes Data 1 – Data 4. It should be remembered that the Data 1 is the low byte and Data 4 the high byte.

MN05013001E

For more information visit: www.EatonElectrical.com

79

Page 83