EZ800/EZD Control Commands
MN05013001E100
Read local inputs IW0This command string enables you to read the local inputs of the EZ800/EZD. The relevant input word is stored in Intel format.
Telegram structure
Table 45: Byte 5 to 6: Data 1 to 2
Byte Meaning Value (hex), sent by
Master Slave
0 Toggle byte Jpage94
1 Command: Read 91
Response:
Read successful C2
Command
rejected C0
2Len 02 02
3Type 01 01
4 Index 00 00
5 Data 1 (Low Byte) 00 JTable 45
6 Data 2 (High Byte) 00 JTable 45
7 – 8 Data 3 – 4 00 00
Data 1 Bit 7 6 5 4 3 2 1 0
I1 0/1
I2 0/1
.. ..
I8 0/1
Data 2 Bit 7 6 5 4 3 2 1 0
I9 0/1
I10 0/1
.. ..
I16 0/1