Read/write image data

Example: Read local inputs IW0

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

Master

 

Slave

0

 

Toggle byte

 

81

 

80

1

 

Command: Read

 

91

 

 

 

 

 

 

 

 

 

 

Response: Read

 

C2

 

 

successful

 

 

 

 

2

 

Len

 

02

 

02

3

 

Type

 

01

 

01

4

 

Index

 

00

 

00

5

 

Data 1

 

00

 

C4

 

 

 

 

 

 

 

6

 

Data 2

00

 

02

 

 

 

 

 

 

 

7

 

Data 3

00

 

00

 

 

 

 

 

 

 

8

 

Data 4

00

 

00

 

 

 

 

 

 

 

J

All values must be transferred as hexadecimal values.

The values Data 1 = C4 and Data 2 = 02 indicate that the inputs I8, I7, I3 and I10 have been set to 1.