Control commands for EZ700

Table 24: Operand overview

Index

Operand

 

 

 

Read

 

Write

(hex)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

Parameters J Table 25

 

 

 

×

 

 

01

 

Control byte J Table 26

 

 

 

×

 

 

 

 

 

 

 

 

 

 

 

02

 

Comparison value 1

 

I12

 

×

 

c1

03

 

Comparison value 2

 

I22

 

×

 

c1

04

 

Gain factor for I1

 

F12

 

×

 

c1

 

 

(I1 = F1 × I1)

 

 

 

 

 

 

05

 

Gain factor for I2

 

F22

 

×

 

c1

 

 

(I2 = F2 × I2)

 

 

 

 

 

 

06

 

Offset for value I1 (I1 = OS +

 

OS2

 

×

 

c1

 

 

actual value at I1)

 

 

 

 

 

 

07

 

Switching hysteresis for

 

HY2

 

×

 

c1

 

 

value I2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)The value can only be written if it is assigned to a constant in the program.

2)A 16-bit value is transferred in data bytes Data 1 – Data 2. It should be remembered that the low byte 1 is in Data 1 (Byte 5) and the high byte 2 (byte 8) in Data 2.

Example: 5327dec = 14CFhex l Data 1 = 0×CF, Data 2 = 0×14

74

For more information visit: www.EatonElectrical.com

MN05013001E

Page 78
Image 78
Eaton Electrical EZ204-DP user manual Index Operand Read Write Hex