Read/write function block data

Analog value comparator/threshold comparator: A1 – A16

Telegram structure

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

J page 44

 

 

 

 

 

 

 

 

 

 

1

 

Command:

 

 

 

 

 

 

Read

89

 

 

 

 

 

 

 

 

 

 

 

 

Write

8D

 

 

 

 

 

 

 

 

 

 

Response:

 

 

 

 

 

 

Read successful

 

 

C2

 

 

 

Write successful

 

 

C1

 

 

 

Command

 

 

C01

 

 

 

rejected

 

 

 

 

2

 

Type

 

8D

 

8D

 

 

 

 

 

 

3

 

Instance2

 

00 – 0F

 

00 – 0F

4

 

Index

Table 24

 

 

 

 

 

 

 

5 – 8

 

Data 1 – 4

depending on index J Table 25

1)Possible causes J page 91

2)EZ provides 16 analog comparators A1 to A16 for use as required. These can be addressed using the instance (0 – F).

MN05013001E