Read/write date and time

For more information visit: www.EatonElectrical.comMN05013001E 95
Read/write date and time
Telegram structure
JPlease also note the relevant description of the real-time
clock provided in the EZ800 manual and the EZD manual.
The latest edition of these manuals are available as PDF
files from the Internet at: www.EatonElectrical.com. EZ800
manual search term: MN05013004E. EZD manual search
term: MN05013005E.
Byte Meaning Value (hex), sent by
Master Slave
0 Toggle byte Jpage94
1 Command
Read 93
Write B3
Response
Read
successful C2
Write
successful C1
Command
rejected C0
2Len 05 05
3 Index 00 00
4 – 8 Data 1 – 5
Read operation 00 JTable 43
For write
operation
JTable43 00