EZ800/EZD Control Commands

Reading receive data network RN1 .. RN32/send data network SN1 .. SN32

EZ-NET allows a point-to-point connection to be implemented between the individual NET stations. The RN and SN data are used for the data exchange (see the EZ800 manual and EZD manual).

The latest editions of these manuals are available as PDF files from the Internet at: www.EatonElectrical.com. EZ800 manual search term: MN05013004E. EZD manual search term:

MN05013005E.

JThe RN SN data of the local device (Index = 0) to which the EZ204-DP is fitted cannot be scanned. In this case the command would be denied with the 0Chex signal.

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

 

J page 94

 

 

1

 

Command: Read

 

91

 

 

 

Response:

 

 

 

 

 

 

 

Read successful

 

C2

 

 

 

 

 

 

 

 

 

 

 

Command

 

C0

 

 

 

rejected

 

 

 

 

2

 

Len

 

04

 

04

 

 

 

 

 

 

 

3

 

Type

 

For RN1 – RN32: 08

 

 

 

 

 

 

 

 

 

 

 

For SN1 – SN32: 0A

 

 

 

 

 

 

 

 

4

 

Index

 

01 – 081

 

01 – 081

5 – 8

 

Data 1 – 4

00

 

J Table 50

 

 

 

 

 

 

 

1) Corresponds to NET-ID

 

 

 

114

For more information visit: www.EatonElectrical.com

MN05013001E

Page 118