Read/write image data
For more information visit: www.EatonElectrical.comMN05013001E 69
Year time switch: Y1 – Y8
The following commands are used to read the logic state of
the individual year time switches.
Telegram structure
Table 21: Byte 5: Data1
Example:
Data1 = 1hex l HY2 is active
Byte Meaning Value (hex), sent by
Master Slave
0 Toggle byte Jpage44
1 Command: Read 88
Response:
Read successful C2
Command
rejected C01
2Len 01 01
3Type 91 91
4 Index 00 00
5 Data 1 (Low Byte) 00 JTable 21
6 – 8 Data 2 – 4 00 00
1) Possible causes Jpage91
Data 1 Bit 7 6 5 4 3 2 1 0
HY1 0/1
HY2 0/1
HY3 0/1
HY4 0/1
HY5 0
HY6 0
HY7 0
HY8 0