Read/write image data

Year time switch: Y1 – Y8

The following commands are used to read the logic state of the individual year time switches.

Telegram structure

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

J page 44

 

 

 

 

 

 

 

 

 

 

1

 

Command: Read

 

88

 

 

 

Response:

 

 

 

 

 

 

 

Read successful

 

C2

 

 

 

 

 

 

 

 

 

 

 

Command

 

C01

 

 

 

rejected

 

 

 

 

2

 

Len

 

01

 

01

3

 

Type

 

91

 

91

 

 

 

 

 

 

 

4

 

Index

00

 

00

 

 

 

 

 

 

 

5

 

Data 1 (Low Byte)

00

 

J Table 21

 

 

 

 

 

 

 

6 – 8

 

Data 2 – 4

00

 

00

 

 

 

 

 

 

 

 

1)Possible causes J page 91 Table 21: Byte 5: Data 1

Data 1

Bit 7

6

5

4

3 2 1 0

HY1

 

 

 

 

0/1

 

 

 

 

 

 

HY2

 

 

 

 

0/1

 

 

 

 

 

 

HY3

 

 

 

 

0/1

 

 

 

 

 

 

HY4

 

 

 

 

0/1

 

 

 

 

 

 

HY5

 

 

 

0

 

 

 

 

 

 

 

HY6

 

 

0

 

 

 

 

 

 

 

 

HY7

 

0

 

 

 

HY8

0

 

 

 

 

 

 

 

 

 

 

Example:

Data 1 = 1hex l HY2 is active

MN05013001E