Control commands for EZ700

Counters: C1 – C16

The following commands are used to read the logic state of the individual counters C1 – C16.

Telegram structure

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

J page 44

 

 

 

 

 

 

 

 

 

 

1

 

Command: Read

 

88

 

 

 

Response:

 

 

 

 

 

 

 

Read successful

 

C2

 

 

 

 

 

 

 

 

 

 

 

Command

 

C01

 

 

 

rejected

 

 

 

 

2

 

Len

 

01

 

01

3

 

Type

 

EE

 

EE

 

 

 

 

 

 

 

4

 

Index

00

 

00

 

 

 

 

 

 

 

5

 

Data 1 (Low Byte)

00

 

J Table 20

 

 

 

 

 

 

 

6

 

Data 2 (Low Byte)

 

00

 

J Table 20

7 – 8

 

Data 3 – 4

 

00

 

00

 

 

 

 

 

 

 

 

1)Possible causes J page 91 Table 11: Byte 5 to 6: Data 1 to 2

Data 1

Bit 7 6 5 4 3 2 1 0

 

 

C1

0/1

 

 

C2

0/1

 

 

...

...

 

 

C8

0/1

Data 2

Bit 7 6 5 4 3 2 1 0

 

 

C9

0/1

 

 

C10

0/1

 

 

...

...

 

 

C16

0/1

 

 