EZ800/EZD Control Commands
MN05013001E104
Example
A voltage signal is present at analog input 1. The required
telegrams for reading the analog value are as follows:
Byte 5 – Data 1 (Low Byte): D9hex
Byte 6 – Data 2 (High Byte): 02hex
J corresponding 16-bit value: 02D9hex = 729 (7.29 V)
Byte Meaning Value (hex), sent by
Master Slave
0 Toggle byte 81 80
1 Command: Read 91
Response: Read
successful C2
2 Len 02 02
3Type 02 02
4 Index 011011
5Data 1 00 D9
6Data 2 00 02
7Data 3 00 00
8Data 4 00 00
1) 01 = Analog input 1