EZ800/EZD Control Commands
MN05013001E158
Table 93: Index 0 – Bit IO
The data in the following table is shown in the Motorola format although it is actually transferred in Intel format.
Table 94: Index 2 – 5, Parameter channels A – D
Example The channel A parameters of year time switch HY14 are to be written.
Bit 7 6 5 4 3 2 1 0
FB output Data 3 – – – – – Q1
1) Status 1 if the switch-on condition is fulfilled.
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Date 2 Date 1
ON y6 y5 y4 y3 y2 y1 y0 m3 m2 m1 m0 d4 d3 d2 d1 d0
Year Month Day
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Date 4 Date 3
OFF y6 y5 y4 y3 y2 y1 y0 m3 m2 m1 m0 d4 d3 d2 d1 d0
Year Month Day
d4 ... d0: Day (1 .. 31), m3 ... m0: Month (1 .. 12), y6 ... y0: Year (0: 2000 .. 99: 2099)
Index 2 – 5, Parameter channels A – D
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Date 2 Date 1
ON 0 0 0 0 0 1 1 0 1 1 0 0 1 1 1 0
Year Month Day
Switch-on time:
Day = 14 = 0Ehex = 0000 1110b
Month = 6 (June) = 06hex = 0000 0110b
Year = 2003 = 03hex = 0000 0011b