Read/write function block data

Table 82: Index 0 – Bit IO

 

 

Bit

7

6

5

4

3

2

1

0

FB input Data 1

 

 

SE1

ED2

EI3

EP4

EN5

FB output Data 3

 

LI6

1)Transfer of manual manipulated variable on status 1

2)Activation of D component on status 1

3)Activation of I component on status 1

4)Activation of P component on status 1

5)Activates the function block on status 1.

6)Status 1 if the value range of the medium-voltage was exceeded

Table 83:

 

Index 1 - Mode

 

 

 

Data 1

 

Operating mode

 

 

 

UNP

 

The manipulated variable is output as a unipolar 12-bit

unipolar

 

value. Corresponding value range for QV 0 to 4095.

BIP

 

The manipulated variable is output as a bipolar 13-bit

bipolar

 

value. Corresponding value range for QV –4096 to

 

 

4095

 

 

 