Control commands for EZ700

Local inputs: I1 – I16

This command string enables you to read the local inputs of the EZ700 basic unit. The relevant input word is stored in Intel format.

Telegram structure

Byte

 

Meaning

Value (hex), sent by

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

Slave

0

 

Toggle byte

J page 44

 

 

 

 

 

 

 

 

 

 

1

 

Command: Read

 

88

 

 

 

Response:

 

 

 

 

 

 

 

Read successful

 

C2

 

 

 

 

 

 

 

 

 

 

 

Command

 

C01)

 

 

 

rejected

 

 

 

 

2

 

Len

 

02

 

02

3

 

Type

 

84

 

84

 

 

 

 

 

 

 

4

 

Index

00

 

00

 

 

 

 

 

 

 

5

 

Data 1 (Low Byte)

00

 

J Table 13

 

 

 

 

 

 

 

6

 

Data 2 (High Byte)

00

 

J Table 13

 

 

 

 

 

 

 

7 – 8

 

Data 3 – 4

00

 

00

 

 

 

 

 

 

 

 

1) Possible causes J page 91

54

For more information visit: www.EatonElectrical.com

MN05013001E

Page 58
Image 58
Eaton Electrical EZ204-DP user manual Local inputs I1