2.Run Insight Diagnostics ("HP Insight Diagnostics" on page 61) and replace failed components as indicated.
1100 Series
Audible Beeps: 2 short
Possible Cause: Both external and internal serial ports are assigned to COM X.
Action: Run the server setup utility and correct the configuration.
1600 Series
1609 - The server may have a failed system battery. Some...
...configuration settings may have been lost and restored to defaults. Refer to server documentation for more information. If you have just replaced the system battery, disregard this message.
Audible Beeps: None
Possible Cause:
Action: Replace battery (or add external battery).
Audible Beeps: None
Possible Cause: The ambient system temperature exceeded acceptable levels.
Action: Lower the room temperature.
...Press Esc key to resume booting without waiting for the system to cool.
WARNING: Pressing Esc is NOT recommended as the system may shutdown unexpectedly.
Audible Beeps: None
Possible Cause: The ambient system temperature exceeded acceptable levels.
Action: Lower the room temperature.
...the Assembly is not installed or multiple fans have failed in the CPU zone. Audible Beeps: None
Possible Cause: Required fans are missing or not spinning.
Action:
1.Check the fans to be sure they are installed and working.
2.Be sure the assembly is properly connected and each fan is properly seated.
3.If the problem persists, replace the failed fans.
4.If a known working replacement fan is not spinning, replace the assembly.
Error messages 109