Return to Section TOC Return to Master TOC

Return to Section TOC Return to Master TOC

Return to Section TOC Return to Master TOC

F-46

TROUBLESHOOTING AND REPAIR

F-46

 

SHUNT FIELD COIL RESISTANCE AND GROUND TEST

 

PROCEDURE

PROCEDURE (continued)

 

 

Shunt coil ground test:

 

1.

Turn the engine off.

 

 

2. Open either or both of the doors on the

7. With the jumper plug or wire feed module

 

machine.

 

unplugged from J5, measure the resistance

NOTE: Secure the doors in the open position using

between either the brown or blue wires and a

good clean chassis ground. The resistance

the door restraint system. If the machine does not

should be very high, 500,000 (500k) Ohms min-

have a door restraint system, remove the doors or

imum.

 

securely restrain them to prevent them from falling

8. If the resistance is still lower than 500,000

closed.

 

Test the shunt coil resistance:

 

(500k) Ohms, check the shunt coil lead wires

 

between the test points and the coils. Also

3.

Remove the jumper plug or wire feed module

check the lead wire connecting the two shunt

 

harness plug from J5. Locate the brown and

coils together inside of the generator. Look for

 

blue wires in J5, (pin numbers 3 and 5). Check

pinched wires and damaged insulation. If the

 

the resistance between these two leads.

low resistance is determined to be between

 

Resistance should measure about 59 ohms at

chassis wound and one of the shunt coils,

 

77°F. (25° C.)

 

replace the coil set.

 

NOTE: It is always best to place probes in the lead

9. Reconnect the wires and replace any covers

 

end of Molex connectors. Molex pins can

that have been removed.

 

 

be easily damaged if probes are inserted in

 

 

 

the connection pin end.

 

*NOTE: The resistance in the copper windings will

4. If the resistance reading is correct, proceed to

change with temperature. Higher temperatures will

 

the Shunt Field Coil Resistance and Ground

 

Test

 

produce slightly higher resistance, and lower tem-

5.

If the resistance is significantly higher than 59*

peratures will produce slightly lower resistance.

 

 

ohms, check the wiring between the test points

 

 

 

and the shunt coils. Check the lead wire con-

 

 

 

necting the two shunt coils together inside the

 

 

 

generator frame. See the wiring diagram and

 

 

 

the internal generator diagram. If these lead

 

 

 

wires and connections are undamaged, one of

 

 

 

the coils is likely open. Replace the shunt field

 

 

 

coil set.

 

 

 

6. If the resistance is significantly lower than 59* Ohms, check the wiring between the test points and the coils for damaged insulation, pinched wires, etc. If the lead wires and insulation are in good condition, replace the shunt coil set.

Return to Section TOC Return to Master TOC

CLASSIC® 300D & 300G

Page 168
Image 168
Lincoln Electric SVM194-A service manual Shunt Field Coil Resistance and Ground Test, Shunt coil ground test