1

Introduction

1.5

Technical Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable Standards

ANSI / IEEE C37.90-1989

IEEE Standard Relays and Relay

 

 

Systems Associated With Elec-

 

 

tric Power Apparatus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 255-4

Single Input Energizing Quantity

 

 

Measuring Relays With Depen-

 

 

dent or Independent Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

General Technical Data

Operating ambient temperature

-20°C to +55°C (-4°F to +131°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storage temperature

-40°Cto+75°C (-40°F to+167°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relative humidity

The average relative humidity

 

 

may be up to 55% outside of

 

 

enclosure for temperatures up to

 

 

40°C, with excursions up to

 

 

95% for a maximum of 96

 

 

hours, without condensation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Altitude

< 1500 meters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

50 Hz or 60 Hz, software select-

 

 

able

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply AC/DC

DC

Rated voltages

48 V (19-56 V),

 

 

125 V (46-144 V),

 

 

250 V (92-288 V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible ripple

<10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC

Rated voltage

120 V rms (102-132 V, 50-60 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power consumption

<15W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Circuit Ratings

Rated current (In)

1 or 5 A, independently for

 

 

phase and ground inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum input current

4 x In continuous

 

 

10 x In for 10 s

 

 

100 x In for 1 s

CT burden

<0.1 VA for 1A CT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<0.5 VA for 5A CT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated voltage (Vn)

115 or 120 volts

Maximum input voltage

for measurement: 1.25 x Vn

 

 

MOV protected at: 2.5 x Vn

VT burden

150kΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trip Circuit

Tripping relays

2 or 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Trip 1, Trip 2, Trip 3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact rating

IEEE/ANSI C37.90-1989, Sec-

 

 

tion 6.7 (Make and carry 30 A for

 

 

at least 2000 duty cycles, resis-

 

 

tive load, interrupted by indepen-

 

 

dent means. Duty cycle:

 

 

200 ms on, 15 s off, 250 V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trip Circuit (continued)

Binary output contacts

2 x N.O. (independent,

(BO1 and BO2)

not rated for tripping)

 

 

Maximum switching voltage

300 VDC, 250 VAC

 

 

Maximum switching current

8 A

 

 

Maximum switching capac-

DC: voltage dependent;

ity (for currents not inter-

50 W at V 70 VDC

rupted by independent

100 W at 48 VDC

means)

270 W at 35 VDC

 

AC: 2000 VA

 

 

Trip source monitor

215 mA for 48 VDC supply

 

63 mA for 125 VDC supply

 

36 mA for 250 VDC supply

 

Source quality checked approxi-

 

mately every 4 minutes

 

 

Isolation

Applicable standards

ANSI/IEEE C37.90-1989,

 

IEC 255-4, IEC 255-5

 

 

Between all circuits (except

2 kV rms, 50/60 Hz, 1 minute

communications interfaces, ana-

 

log inputs and outputs) and

 

ground, and between these cir-

 

cuits.

 

 

 

Between communications inter-

500 VDC, 1 minute

faces, analog inputs and outputs

 

and ground, and between these

 

circuits

 

 

 

Across open contacts rated for

1500 V rms, 50/60 Hz, 1 minute

tripping

 

 

 

Across open contacts not rated

1000 V rms, 50/60 Hz, 1 minute

for tripping

 

 

 

Impulse

Applicable standards

IEC 255-4, IEC 255-5

 

 

For all circuits (except communi-

class 3, 5 kV, 1.2/50 μs, 0.5 J

cations interfaces, analog

 

inputs and outputs), transverse

 

and common mode

 

 

 

RS-485 and local communica-

class 1, 0 kV

tions interfaces, analog I/Os

 

 

 

Electrostatic Discharge

Applicable standards

IEC 801-2 (test without cover)

 

 

Contact discharge

class 3, 6 kV

 

 

Air discharge

class 3, 8 kV

 

 

Surge Withstand Capability

Applicable standards

ANSI/IEEE C37.90-1989,

 

IEC 255-4, IEC 255-22-1,

 

IEC 41B (CO) 53

 

 

For all circuits except communi-

ANSI: Oscillatory and Fast Tran-

cations interfaces, analog

sient, transverse and common

inputs and outputs

mode

 

IEC: Class 3, 2.5 kV

 

 

For RS-485 interface, analog

IEC: Class 1, 0.5 kV

inputs and outputs

 

 

 

Electromagnetic Field

Applicable standards

ANSI/IEEE C37.90.2

 

 

All six faces

10 V/m (+100%, -0%),

 

2-1000 MHz

4

Siemens Energy & Automation, Inc.

Page 10
Image 10
Siemens SG8158-00 manual Technical Specifications