1
Introduction
1.5 | Technical Specifications | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Applicable Standards | ||||||||||||||
ANSI / IEEE | IEEE Standard Relays and Relay | ||||||||||||||
|
| Systems Associated With Elec- | |||||||||||||
|
| tric Power Apparatus | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
IEC | Single Input Energizing Quantity | ||||||||||||||
|
| Measuring Relays With Depen- | |||||||||||||
|
| dent or Independent Time | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| General Technical Data | ||||||||||||||
Operating ambient temperature | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Storage temperature | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Relative humidity | The average relative humidity | ||||||||||||||
|
| may be up to 55% outside of | |||||||||||||
|
| enclosure for temperatures up to | |||||||||||||
|
| 40°C, with excursions up to | |||||||||||||
|
| 95% for a maximum of 96 | |||||||||||||
|
| hours, without condensation. | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Altitude | < 1500 meters | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Frequency | 50 Hz or 60 Hz, software select- | ||||||||||||||
|
| able | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Power Supply AC/DC | ||||||||||||||
DC | Rated voltages | 48 V | |||||||||||||
|
| 125 V | |||||||||||||
|
| 250 V | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Permissible ripple | <10% |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC | Rated voltage | 120 V rms | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Power consumption | <15W | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Input Circuit Ratings | ||||||||||||||
Rated current (In) | 1 or 5 A, independently for | ||||||||||||||
|
| phase and ground inputs | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Maximum input current | 4 x In continuous | ||||||||||||||
|
| 10 x In for 10 s | |||||||||||||
|
| 100 x In for 1 s | |||||||||||||
CT burden | <0.1 VA for 1A CT | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| <0.5 VA for 5A CT | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Rated voltage (Vn) | 115 or 120 volts | ||||||||||||||
Maximum input voltage | for measurement: 1.25 x Vn | ||||||||||||||
|
| MOV protected at: 2.5 x Vn | |||||||||||||
VT burden | 150kΩ | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Trip Circuit | ||||||||||||||
Tripping relays | 2 or 3 | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Contact configuration |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
(Trip 1, Trip 2, Trip 3) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Contact rating | IEEE/ANSI | ||||||||||||||
|
| tion 6.7 (Make and carry 30 A for | |||||||||||||
|
| at least 2000 duty cycles, resis- | |||||||||||||
|
| tive load, interrupted by indepen- | |||||||||||||
|
| dent means. Duty cycle: | |||||||||||||
|
| 200 ms on, 15 s off, 250 V) | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Trip Circuit (continued)
Binary output contacts | 2 x N.O. (independent, |
(BO1 and BO2) | not rated for tripping) |
|
|
Maximum switching voltage | 300 VDC, 250 VAC |
|
|
Maximum switching current | 8 A |
|
|
Maximum switching capac- | DC: voltage dependent; |
ity (for currents not inter- | 50 W at V ≥70 VDC |
rupted by independent | 100 W at 48 VDC |
means) | 270 W at 35 VDC |
| AC: 2000 VA |
|
|
Trip source monitor | 215 mA for 48 VDC supply |
| 63 mA for 125 VDC supply |
| 36 mA for 250 VDC supply |
| Source quality checked approxi- |
| mately every 4 minutes |
|
|
Isolation | |
Applicable standards | ANSI/IEEE |
| IEC |
|
|
Between all circuits (except | 2 kV rms, 50/60 Hz, 1 minute |
communications interfaces, ana- |
|
log inputs and outputs) and |
|
ground, and between these cir- |
|
cuits. |
|
|
|
Between communications inter- | 500 VDC, 1 minute |
faces, analog inputs and outputs |
|
and ground, and between these |
|
circuits |
|
|
|
Across open contacts rated for | 1500 V rms, 50/60 Hz, 1 minute |
tripping |
|
|
|
Across open contacts not rated | 1000 V rms, 50/60 Hz, 1 minute |
for tripping |
|
|
|
Impulse | |
Applicable standards | IEC |
|
|
For all circuits (except communi- | class 3, 5 kV, 1.2/50 μs, 0.5 J |
cations interfaces, analog |
|
inputs and outputs), transverse |
|
and common mode |
|
|
|
class 1, 0 kV | |
tions interfaces, analog I/Os |
|
|
|
Electrostatic Discharge | |
Applicable standards | IEC |
|
|
Contact discharge | class 3, 6 kV |
|
|
Air discharge | class 3, 8 kV |
|
|
Surge Withstand Capability | |
Applicable standards | ANSI/IEEE |
| IEC |
| IEC 41B (CO) 53 |
|
|
For all circuits except communi- | ANSI: Oscillatory and Fast Tran- |
cations interfaces, analog | sient, transverse and common |
inputs and outputs | mode |
| IEC: Class 3, 2.5 kV |
|
|
For | IEC: Class 1, 0.5 kV |
inputs and outputs |
|
|
|
Electromagnetic Field | |
Applicable standards | ANSI/IEEE C37.90.2 |
|
|
All six faces | 10 V/m (+100%, |
|
4 | Siemens Energy & Automation, Inc. |