Siemens SG8158-00 manual Isgs Settings Worksheet for Date Set B

Models: SG8158-00

1 121
Download 121 pages 35.55 Kb
Page 106
Image 106

S

ISGS Settings Worksheet for

Date:

Set B

 

 

 

B1900

Directional Time Overcurrent (67)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B1901

Function 67

 

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

B1902

Curve 67

 

Inverse

Short Inverse

 

Long Inverse

Moderately

 

 

Inverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Custom

Very Inverse

 

Extremely Inverse

Definite Inverse

 

 

 

 

 

 

 

 

 

 

 

 

Slightly Inverse

I2T without Limit

 

 

 

 

B1903

Pickup 67

5 A CT

0.5 A

Range:

0.5-20 A

(0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

 

 

1 A CT

0.1 A

Range:

0.1-4 A

(0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

B1905

Time Dial 67

 

0.1

Range:

0.1-9.9

(0.1 steps)

 

 

 

 

 

 

 

 

 

 

 

 

B1906

Filter 67

 

rms

 

 

 

fundamental

 

 

 

 

 

 

 

 

 

 

B1907

Impedance 67

 

45°

Range:

0-90° (1° steps)

 

°

 

 

 

 

 

 

 

 

 

 

B1908

Direction 67

 

Normal

 

 

 

Reverse

 

 

 

 

 

 

 

 

 

1910

Freeze Waveform 1 67

 

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

1911

Freeze Waveform 2 67

 

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

B2000

Directional Neutral Time Overcurrent (67N)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2001

Function 67N

 

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

B2002

Curve 67N

 

Inverse

Short Inverse

 

Long Inverse

Moderately

 

 

Inverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Custom

Very Inverse

 

Extremely Inverse

Definite Inverse

 

 

 

 

 

 

 

 

 

 

 

 

Slightly Inverse

I2T without Limit

 

 

 

 

B2003

Pickup 67N

5 A CT

0.5 A

Range: 0.5-20 A (0.1 A steps)

 

A

 

(PU point is 1.06

1 A CT

 

 

 

 

 

 

 

 

0.1 A

Range:

0.1-4 A

(0.1 A steps)

 

A

 

of PU setting).

 

 

 

 

 

 

 

 

 

 

 

B2005

Time Dial 67N

 

0.1

Range:

0.1-9.9

(0.1 steps)

 

 

 

 

 

 

 

 

 

 

 

 

B2006

Filter 67N

 

rms

 

 

 

fundamental

 

 

 

 

 

 

 

 

 

 

B2007

Impedance 67N

 

45°

Range:

0-90° (1° steps)

 

°

 

 

 

 

 

 

 

 

 

 

B2008

Direction 67N

 

Normal

 

 

 

Reverse

 

 

 

 

 

 

 

 

 

2010

Freeze Waveform 1 67N

 

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

2011

Freeze Waveform 2 67N

 

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

S-20

Siemens Energy & Automation, Inc.

Page 106
Image 106
Siemens SG8158-00 manual Isgs Settings Worksheet for Date Set B